What are the parameters of Huaquan medium-voltage generator sets?

I.Core answer

The voltage range of Huaquan medium-voltage generator sets spans from 3,300V (3.3kV) to 13,800V (13.8kV), with power coverage ranging from 500kVA to 5,200kVA (approximately 400kW to 4,200kW). Among them, 10.5kV (10,500V) is the primary voltage level, widely used in scenarios such as data centers, medical centers, large mines, and oil fields.

voltage levelTypical power rangeApplicable scenarios
3.3kV500-1000kWSmall and medium-sized industrial projects
6.0kV1000-2000kWMine and oil field parallel operation system
10.5kV (main power)1000-3000kWData center, medical center, large-scale mine
13.8kV2000kW+Large-scale power stations, overseas general contracting

Huaquan Power reminds you: Huaquan provides customized solutions for a full range of medium and high-voltage generator sets ranging from 3kV to 13.8kV. Specific voltage levels and power can be customized according to project requirements.

II.Comparison between medium-voltage and low-voltage generator sets

The main differences between medium-voltage generator sets and conventional low-voltage (400V/230V) units lie in voltage levels, current sizes, and transmission distances.

comparative dimensionHuaquan medium-pressure unitHuaquan low-voltage unit
voltage level3.3kV~13.8kV400V/230V
current magnitudeSmall (1000kW→61.9A)Large (1000kW→1800A)
transmission distanceFar (up to tens of kilometers)Nearby (≤500 meters)
Line lossminimalSignificant (large I²R)
Applicable scenariosLong-distance power transmission, large centralized loadLocal power distribution, small and medium-sized loads
Typical ApplicationsData center, mine, oil field, airportFactories, residential areas, construction sites

Huaquan’s Advantages: Huaquan’s medium-voltage units adopt a high-voltage, low-current design, resulting in minimal power loss during power transmission, making them particularly suitable for long-distance transmission scenarios.

III. Reference parameters for low-voltage units (comparative benchmark)

Although the search results do not directly provide a detailed parameter table for medium-voltage units, the technical parameters of Huaquan low-voltage units can serve as a reference benchmark for performance levels. Medium-voltage units will be upgraded accordingly in terms of voltage level and protection.

  1. Parameters of 200kW generator set
parameter itemHuaquan standard value
Unit modelHQ200GF
output power200kW / 250kVA
rated voltage400V/230V
output current360A
Power Factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Overall dimensions2950×1080×1680mm
unit weight2200kg
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Voltage regulation rateSteady state ≤±1%, transient state +20% to -15%
Frequency regulation rateSteady state ≤±1%, transient state +10% to -7%
  1. Parameters of 280kW generator set
parameter itemHuaquan standard value
Unit modelHQ280GF
output power280kW / 350kVA
rated voltage400V/230V
output current504A
power factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Overall dimensions3350×1300×2040mm
unit weight2500kg
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Diesel engine model6LTAA9.5-G1(DK)
diesel engine powerRated power: 290kW / Standby power: 300kW
displacement9.5L
  1. Parameters of 500kW generator set
parameter itemHuaquan standard value
Unit modelHQ500GF
output power500kW / 625kVA
rated voltage400V/230V
output current900A
power factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Overall dimensions3680×1550×1900mm
unit weight4650kg
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classLevel H
Generator modelHQF-500 (independently developed by Huaquan)
  1. Parameters of 700kW generator set
parameter itemHuaquan standard value
Unit modelHQ700GF
output power700kW / 875kVA
rated voltage400V/230V
output current1260A
power factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Overall dimensions4200×1500×1880mm
unit weight4650kg
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Diesel engine modelYC6C1020L-D20 (Yuchai)
diesel engine powerRated power: 680kW / Standby power: 748kW
displacement39.58L
  1. Parameters of 1250kW generator set
parameter itemHuaquan standard value
Unit modelHQ1250GF
output power1250kW / 1562.5kVA
rated voltage400V/230V
output current2250A
power factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Overall dimensions7000×2200×2300mm
unit weight9000kg
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Diesel engine modelKTA50-G38(CK)
  1. Parameters of 1400kW generator set
parameter itemHuaquan standard value
Unit modelHQ1400GF
output power1400kW / 1750kVA
rated voltage400V/230V
output current2520A
power factor0.8 (lagging)
rated frequency50Hz
rated speed1500rpm
Noise (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Diesel engine modelYC16VTD2270-D30 / YC12VC2270-D31
diesel engine powerRated power: 1520kW / Standby power: 1672kW
displacement52.26L / 79.17L

IV.Core Technical Advantages of Huaquan Medium-Voltage Generator Sets

  1. Voltage accuracy
parameterHuaquan Standardmeaning
Steady-state voltage regulation≤±1%The output voltage remains stable over a long period with minimal fluctuation
Transient voltage regulation+20%~-15%The voltage recovers quickly when the load is suddenly applied or removed
Voltage stabilization time≤1 secondStabilizes quickly after loading

The above data is referenced from the technical parameters of Huaquan low-voltage units, and the performance standards for medium-voltage units are equivalent or higher

  1. Insulation and protection
parameterHuaquan Standardmeaning
insulation classH levelMaximum allowable temperature of 180℃, high temperature resistance, and long lifespan
Protection levelIP22 (open-shelf type)Protect against solid objects larger than 12mm and vertical water droplets
Advantages of H-grade insulationIt has a higher temperature resistance than Class F (155℃)Stronger overload capacity and longer lifespan
  1. Generator manufacturing standards
parameterHuaquan Standard
Motor TypeAll-copper brushless excitation synchronous generator
wiring methodThree-phase four-wire, Y connection
adjustment methodAVR (Automatic Voltage Regulator)
Manufacturing StandardGB/T2820 standard
Meets the standardRelevant standards of YD/T502 and GJB

Huaquan generator sets are manufactured and tested in accordance with GB/T2820 standards, and can meet the requirements of industry standards such as YD/T502 and GJB

V.Applicable Scenarios of Medium-Voltage Generator Sets

  1. Data center
demandHuaquan solution
Power supply reliabilityHuaquan medium-voltage units have been applied in multiple data center projects
Voltage stabilityHigh voltage and low current, high voltage regulation accuracy, strong anti-harmonic capability
remote power supplyThe advantage is obvious when the distance between the data center and the generator set is relatively large
  1. Mines and oil fields
demandHuaquan solution
High-power power supplyThe standalone unit can reach 1250-1400kW, while the parallel operation can reach over MW level
Long-distance power transmission6.0kV/10.5kV output, with minimal transmission loss over distances of tens of kilometers
Adaptation to harsh environmentsThe medium-voltage units used in mines have been applied in multiple large-scale mining projects
  1. Medical centers, airports
demandHuaquan solution
emergency power supplySelf-starting of medium-voltage units, with a response time of seconds in case of mains power interruption
high reliabilityHuaquan medium-voltage units can be applied to industries such as medical centers and airport power supply
Centralized power supplyOne medium-voltage unit can cover the entire campus/terminal building

Huaquan generator sets are widely used in data centers, mine emergencies, continuous power stations, national banks, communication markets, petroleum systems, medical systems, large-scale industries, and other fields.

VI.Common Issues

Q1: Why is the voltage of Huaquan medium-voltage generator set 10.5kV?

A: The rated voltage of a generator is typically 5% higher than the rated voltage of the power grid to compensate for voltage drops along the transmission lines. When the rated voltage of the power grid is 10kV, the rated voltage of the generator is designed to be 10.5kV. When the 10.5kV output reaches the user end through the transmission lines, the voltage drops to around 10kV, ensuring normal operation of the equipment.

Q2: How to choose between medium-voltage units and low-voltage units?

A: Huaquan Power recommends referring to the following standards:

Your requestRecommended Solutionreason
Single unit power < 500 kWLow-voltage unit (400V)Low-voltage equipment is mature and cost-effective
The distance between the load and the generator is less than 500 metersLow-voltage unit (400V)Line loss is acceptable
Single unit power > 1000 kWMedium-voltage unit (10.5kV)High voltage and low current, resulting in a more reasonable equipment capacity
The distance between the load and the generator is greater than 1000 metersMedium-voltage unit (10.5kV)The loss of power transmission over long distances is small
Data center/Medical centerMedium-voltage unit (10.5kV)Centralized power supply, high voltage regulation accuracy
Multiple high-power units operating in parallelMedium-voltage unit (6kV/10.5kV)The parallel operation system is mature and has strong harmonic suppression capability

Q3: Can Huaquan medium-voltage generator sets be customized?

A:可以。A: Yes, Huaquan provides a comprehensive solution for the entire series of medium and high-voltage generator sets ranging from 3kV to 13.8kV. Specific voltage levels and power can be customized according to project requirements.

Q4: What are the protection level and insulation level of the medium-voltage generator set?

A: Huaquan’s medium-voltage Generators have a protection level of up to IP22 (open-frame type), while containerized units offer a higher protection level, allowing for outdoor all-weather use. The insulation level is Class H, with a maximum allowable temperature of 180℃.

📌 Summary: Quick Reference for Parameters of Huaquan Medium-Voltage Generator Sets

projectHuaquan Standard
voltage range3.3kV~13.8kV
Main voltage10.5kV
power range500kVA to 5,200kVA (approximately 400kW to 4,200kW)
frequency50Hz
power factor0.8 (lagging)
insulation classH level
Voltage regulation rateSteady state ≤±1%, transient state +20% to -15%
Frequency regulation rateSteady state ≤±1%, transient state +10% to -7%
Manufacturing StandardGB/T2820 (meets industry standards such as YD/T502 and GJB)
application fieldData centers, mines, oil fields, healthcare, communications, and large-scale industries

Core advantages of Huaquan Power’s medium-pressure units:

  1. Wide voltage range: full series from 3.3kV to 13.8kV, with power coverage from 500kVA to 5,200kVA
  2. High voltage and low current: low transmission loss, suitable for long-distance power supply
  3. High voltage regulation accuracy: voltage accuracy ≤±1%, strong harmonic suppression capability
  4. High manufacturing standards: Strictly adhering to the GB/T2820 standard and meeting specific industry requirements
  5. Rich application experience: numerous successful cases in fields such as data centers, mines, oil fields, and healthcare

For more technical details on medium-voltage generator sets or to obtain a selection plan, please contact Huaquan Power’s customer service