< img height="1" width="1" style="display:none" src="https://www.facebook.com/tr?id=818233107660385&ev=PageView&noscript=1" />
x
Hantar Pertanyaan Anda Hari Ini
Sebut Harga Pantas

What are the parameters of Huaquan medium-voltage generator sets?

I.Core answer

The voltage range of Huaquan medium-voltage generator sets spans from 3,300V (3.3kV) to 13,800V (13.8kV), with power coverage ranging from 500kVA to 5,200kVA (approximately 400kW to 4,200kW). Antaranya, 10.5kV (10,500V) is the primary voltage level, widely used in scenarios such as data centers, medical centers, large mines, and oil fields.

voltage levelTypical power rangeSenario yang berkenaan
3.3kV500-1000kWSmall and medium-sized industrial projects
6.0kV1000-2000kWMine and oil field parallel operation system
10.5kV (main power)1000-3000kWPusat data, medical center, large-scale mine
13.8kV2000kW+Large-scale power stations, overseas general contracting

Huaquan Power reminds you: Huaquan provides customized solutions for a full range of medium and high-voltage generator sets ranging from 3kV to 13.8kV. Specific voltage levels and power can be customized according to project requirements.

II.Comparison between medium-voltage and low-voltage generator sets

The main differences between medium-voltage generator sets and conventional low-voltage (400V/230V) units lie in voltage levels, current sizes, and transmission distances.

comparative dimensionHuaquan medium-pressure unitHuaquan low-voltage unit
voltage level3.3kV~13.8kV400V/230V
current magnitudeKecil (1000kW→61.9A)Large (1000kW→1800A)
transmission distanceFar (up to tens of kilometers)Nearby (≤500 meters)
Line lossminimalSignificant (large I²R)
Senario yang berkenaanLong-distance power transmission, large centralized loadLocal power distribution, small and medium-sized loads
Typical ApplicationsPusat data, mine, oil field, airportkilang, kawasan perumahan, tapak pembinaan

Huaquan’s Advantages: Huaquan’s medium-voltage units adopt a high-voltage, low-current reka bentuk, resulting in minimal power loss during power transmission, making them particularly suitable for long-distance transmission scenarios.

III. Reference parameters for low-voltage units (comparative benchmark)

Although the search results do not directly provide a detailed parameter table for medium-voltage units, the technical parameters of Huaquan low-voltage units can serve as a reference benchmark for performance levels. Medium-voltage units will be upgraded accordingly in terms of voltage level and protection.

  1. Parameters of 200kW generator set
parameter itemHuaquan standard value
Unit modelHQ200GF
kuasa keluaran200kW / 250kVA
rated voltage400V/230V
arus keluaran360A
Faktor Kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
Overall dimensions2950×1080×1680mm
unit weight2200kg
bising (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Voltage regulation rateSteady state ≤±1%, transient state +20% kepada -15%
Frequency regulation rateSteady state ≤±1%, transient state +10% kepada -7%
  1. Parameters of 280kW generator set
parameter itemHuaquan standard value
Unit modelHQ280GF
kuasa keluaran280kW / 350kVA
rated voltage400V/230V
arus keluaran504A
faktor kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
Overall dimensions3350×1300×2040mm
unit weight2500kg
bising (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Model enjin diesel6LTAA9.5-G1(DK)
diesel engine powerRated power: 290kW / Kuasa siap sedia: 300kW
anjakan9.5L
  1. Parameters of 500kW generator set
parameter itemHuaquan standard value
Unit modelHQ500GF
kuasa keluaran500kW / 625kVA
rated voltage400V/230V
arus keluaran900A
faktor kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
Overall dimensions3680×1550×1900mm
unit weight4650kg
bising (at 7m)95dB(A)
Protection levelIP22
insulation classLevel H
Generator modelHQF-500 (independently developed by Huaquan)
  1. Parameters of 700kW generator set
parameter itemHuaquan standard value
Unit modelHQ700GF
kuasa keluaran700kW / 875kVA
rated voltage400V/230V
arus keluaran1260A
faktor kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
Overall dimensions4200×1500×1880mm
unit weight4650kg
bising (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Model enjin dieselYC6C1020L-D20 (Yuchai)
diesel engine powerRated power: 680kW / Kuasa siap sedia: 748kW
anjakan39.58L
  1. Parameters of 1250kW generator set
parameter itemHuaquan standard value
Unit modelHQ1250GF
kuasa keluaran1250kW / 1562.5kVA
rated voltage400V/230V
arus keluaran2250A
faktor kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
Overall dimensions7000×2200×2300mm
unit weight9000kg
bising (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Model enjin dieselKTA50-G38(CK)
  1. Parameters of 1400kW generator set
parameter itemHuaquan standard value
Unit modelHQ1400GF
kuasa keluaran1400kW / 1750kVA
rated voltage400V/230V
arus keluaran2520A
faktor kuasa0.8 (lagging)
rated frequency50Hz
kelajuan dinilai1500rpm
bising (at 7m)95dB(A)
Protection levelIP22
insulation classH level
Model enjin dieselYC16VTD2270-D30 / YC12VC2270-D31
diesel engine powerRated power: 1520kW / Kuasa siap sedia: 1672kW
anjakan52.26L / 79.17L

IV.Core Technical Advantages of Huaquan Medium-Voltage Generator Sets

  1. Voltage accuracy
parameterHuaquan Standardmeaning
Steady-state voltage regulation≤±1%The output voltage remains stable over a long period with minimal fluctuation
Transient voltage regulation+20%~-15%The voltage recovers quickly when the load is suddenly applied or removed
Voltage stabilization time≤1 secondStabilizes quickly after loading

The above data is referenced from the technical parameters of Huaquan low-voltage units, and the performance standards for medium-voltage units are equivalent or higher

  1. Insulation and protection
parameterHuaquan Standardmeaning
insulation classH levelMaximum allowable temperature of 180℃, high temperature resistance, and long lifespan
Protection levelIP22 (open-shelf type)Protect against solid objects larger than 12mm and vertical water droplets
Advantages of H-grade insulationIt has a higher temperature resistance than Class F (155℃)Stronger overload capacity and longer lifespan
  1. Generator manufacturing standards
parameterHuaquan Standard
Motor TypeAll-copper brushless excitation synchronous generator
wiring methodThree-phase four-wire, Y connection
adjustment methodAVR (Pengatur Voltan Automatik)
Manufacturing StandardGB/T2820 standard
Meets the standardRelevant standards of YD/T502 and GJB

Huaquan generator sets are manufactured and tested in accordance with GB/T2820 standards, and can meet the requirements of industry standards such as YD/T502 and GJB

V.Applicable Scenarios of Medium-Voltage Generator Sets

  1. Pusat data
permintaanHuaquan solution
Power supply reliabilityHuaquan medium-voltage units have been applied in multiple data center projects
Kestabilan voltanHigh voltage and low current, high voltage regulation accuracy, strong anti-harmonic capability
remote power supplyThe advantage is obvious when the distance between the data center and the generator set is relatively large
  1. Mines and oil fields
permintaanHuaquan solution
High-power power supplyThe standalone unit can reach 1250-1400kW, while the parallel operation can reach over MW level
Long-distance power transmission6.0kV/10.5kV output, with minimal transmission loss over distances of tens of kilometers
Adaptation to harsh environmentsThe medium-voltage units used in mines have been applied in multiple large-scale mining projects
  1. Medical centers, airports
permintaanHuaquan solution
bekalan kuasa kecemasanSelf-starting of medium-voltage units, with a response time of seconds in case of mains power interruption
high reliabilityHuaquan medium-voltage units can be applied to industries such as medical centers and airport power supply
Centralized power supplyOne medium-voltage unit can cover the entire campus/terminal building

Huaquan generator sets are widely used in pusat data, mine emergencies, continuous power stations, national banks, communication markets, petroleum systems, medical systems, industri berskala besar, dan bidang lain.

VI.Common Issues

S1: Why is the voltage of Huaquan medium-voltage generator set 10.5kV?

A: The rated voltage of a generator is typically 5% higher than the rated voltage of the power grid to compensate for voltage drops along the transmission lines. When the rated voltage of the power grid is 10kV, the rated voltage of the generator is designed to be 10.5kV. When the 10.5kV output reaches the user end through the transmission lines, the voltage drops to around 10kV, ensuring normal operation of the equipment.

S2: How to choose between medium-voltage units and low-voltage units?

A: Huaquan Power recommends referring to the following standards:

Your requestPenyelesaian Disyorkanreason
Single unit power < 500 kWLow-voltage unit (400V)Low-voltage equipment is mature and cost-effective
The distance between the load and the generator is less than 500 meterLow-voltage unit (400V)Line loss is acceptable
Single unit power > 1000 kWMedium-voltage unit (10.5kV)High voltage and low current, resulting in a more reasonable equipment capacity
The distance between the load and the generator is greater than 1000 meterMedium-voltage unit (10.5kV)The loss of power transmission over long distances is small
Data center/Medical centerMedium-voltage unit (10.5kV)Centralized power supply, high voltage regulation accuracy
Multiple high-power units operating in parallelMedium-voltage unit (6kV/10.5kV)The parallel operation system is mature and has strong harmonic suppression capability

S3: Can Huaquan medium-voltage generator sets be customized?

A可以。A: ya, Huaquan provides a comprehensive solution for the entire series of medium and high-voltage generator sets ranging from 3kV to 13.8kV. Specific voltage levels and power can be customized according to project requirements.

Q4: What are the protection level and insulation level of the medium-voltage generator set?

A: Huaquan’s medium-voltage Penjana have a protection level of up to IP22 (open-frame type), while containerized units offer a higher protection level, allowing for outdoor all-weather use. The insulation level is Class H, with a maximum allowable temperature of 180℃.

📌 Summary: Quick Reference for Parameters of Huaquan Medium-Voltage Generator Sets

projectHuaquan Standard
voltage range3.3kV~13.8kV
Main voltage10.5kV
julat kuasa500kVA to 5,200kVA (approximately 400kW to 4,200kW)
kekerapan50Hz
faktor kuasa0.8 (lagging)
insulation classH level
Voltage regulation rateSteady state ≤±1%, transient state +20% kepada -15%
Frequency regulation rateSteady state ≤±1%, transient state +10% kepada -7%
Manufacturing StandardGB/T2820 (meets industry standards such as YD/T502 and GJB)
medan permohonanPusat data, mines, medan minyak, penjagaan kesihatan, communications, and large-scale industries

Core advantages of Huaquan Power’s medium-pressure units:

  1. Wide voltage range: full series from 3.3kV to 13.8kV, with power coverage from 500kVA to 5,200kVA
  2. High voltage and low current: low transmission loss, suitable for long-distance power supply
  3. High voltage regulation accuracy: voltage accuracy ≤±1%, strong harmonic suppression capability
  4. High manufacturing standards: Strictly adhering to the GB/T2820 standard and meeting specific industry requirements
  5. Rich application experience: numerous successful cases in fields such as data centers, mines, medan minyak, and healthcare

For more technical details on medium-voltage generator sets or to obtain a selection plan, please contact Huaquan Power’s customer service