This page provides detailed fuel consumption data for a 200kW Diesel Generator. All data is based on Huaquan Power test reports and Cummins/Perkins engine shop manuals.
200kW Fuel Consumption Table
| Load (%) | Power Output | Fuel Consumption (L/h) | Fuel Consumption (kg/h) | Runtime (500L Tank) |
|---|---|---|---|---|
| 25% | 50 kW | 10 L/h | 8 kg/h | 50 hours |
| 50% | 100 kW | 22 L/h | 18 kg/h | 22 hours |
| 75% | 150 kW | 35 L/h | 29 kg/h | 14 hours |
| 100% | 200 kW | 50 L/h | 42 kg/h | 10 hours |
| 110% | 220 kW | 55 L/h | 46 kg/h | 9 hours |
Factors Specific to 200kW Generators
For 200kW generators, pay attention to:
- Engine Selection: Cummins QSK series offers 5-8% better fuel efficiency than comparable engines
- Ambient Temperature: Above 40°C, fuel consumption increases by 3-5%
- Altitude: Above 1000m, diesel engines don’t lose power (unlike gas), but cooling efficiency drops
- Maintenance: Replace fuel filters every 500h to maintain optimal consumption
Real-World Case: Huaquan Project Data
In Huaquan’s global projects, we’ve measured actual fuel consumption for 200kW generators:
| Project Location | Application | Measured Fuel (L/h) | Notes |
|---|---|---|---|
| Southeast Asia | Manufacturing plant | 34 L/h @ 75% load | With cooling load included |
| Middle East | Data center | 36 L/h @ 75% load | High ambient temperature |
For a personalized fuel cost estimate based on your local diesel price and operating hours, contact our technical team.
⚡ Explore Related Solutions
- 🏭 200kW Diesel Generator
- 🏭 500kW Diesel Generator
- 🏭 1000kW Diesel Generator
- 🏭 500kW YC Diesel Generator
- 🔧 KMS (Cummins/Doosan) Series
- 📋 Diesel Generator Sets
- 📋 Order Process — How to Buy
- 📋 Contact Us
💡 Need a customized solution? Contact our engineering team for project-specific recommendations.