This page provides detailed fuel consumption data for a 500kW Générateur diesel. All data is based on Huaquan Power test reports and Cummins/Perkins engine shop manuals.
500kW Fuel Consumption Table
| Charger (%) | Puissance de sortie | Consommation de carburant (L/heure) | Consommation de carburant (kg/heure) | Durée d'exécution (500L Tank) |
|---|---|---|---|---|
| 25% | 125 kW | 26 L/heure | 22 kg/heure | 19 heures |
| 50% | 250 kW | 56 L/heure | 47 kg/heure | 8 heures |
| 75% | 375 kW | 89 L/heure | 75 kg/heure | 5 heures |
| 100% | 500 kW | 125 L/heure | 106 kg/heure | 4 heures |
| 110% | 550 kW | 137 L/heure | 116 kg/heure | 3 heures |
Factors Specific to 500kW Générateurs
For 500kW generators, pay attention to:
- Engine Selection: Cummins QSK series offers 5-8% better fuel efficiency than comparable engines
- Température ambiante: Au dessus de 40°C, fuel consumption increases by 3-5%
- Altitude: Above 1000m, diesel engines don’t lose power (unlike gas), but cooling efficiency drops
- Entretien: Replace fuel filters every 500h to maintain optimal consumption
Real-World Case: Huaquan Project Data
In Huaquan’s global projects, we’ve measured actual fuel consumption for 500kW generators:
| Project Location | Application | Measured Fuel (L/heure) | Remarques |
|---|---|---|---|
| Asie du Sud-Est | Usine de fabrication | 86 L/h @ 75% charger | With cooling load included |
| Moyen-Orient | Centre de données | 90 L/h @ 75% charger | Température ambiante élevée |
For a personalized fuel cost estimate based on your local diesel price and operating hours, contact our technical team.
⚡ Explorez les solutions associées
- 🏭 500Générateur diesel kW
- 🏭 1000Générateur diesel kW
- 🏭 500Générateur diesel YC kW
- 🔧 KMS (Cummins/Doosan) Série
- 📋 Groupes électrogènes diesel
- 📋 Processus de commande – Comment acheter
- 📋 Contactez-nous
💡 Besoin d'une solution personnalisée? Contactez notre équipe d'ingénierie pour des recommandations spécifiques à un projet.