Choosing the right diesel generator size for your Maison means the difference between powering everything comfortably and having a generator that trips breakers or wastes fuel. The most common mistake homeowners make is buying a generator based on square footage or “what the neighbor has” instead of calculating actual electrical load.
This guide provides a step-by-step method to calculate your home’s power requirements, understand starting vs running wattage, and select the optimal diesel generator size.
Étape 1: List Every Appliance You Need to Power
Not everything needs to run during an outage. Separate appliances into three tiers:
| Étage | Description | Charge typique |
|---|---|---|
| Étage 1: Essentiel | Réfrigérateur, congélateur, pompe de puits, sump pump, furnace blower, équipement médical, lumières, router/modem | 3-5 KW |
| Étage 2: Comfort | Étage 1 + window AC or one central AC unit, chauffe-eau, micro-ondes, washer, TV, ordinateurs | 7-12 KW |
| Étage 3: Full Home | Everything including central AC, electric oven, electric dryer, pool pump, EV charger | 15-30+ KW |
Étape 2: Calculate Running and Starting Wattage
Every motor-driven appliance (réfrigérateur, CA, pompe de puits, furnace blower) draws 3-7× its running wattage for 1-3 seconds at startup. This starting surge (inrush current) must be covered by the generator’s surge rating.
| Appareil | Watts courants | Watts de démarrage |
|---|---|---|
| Refrigerator/freezer (21 cu ft) | 700 | 2,200 |
| Chest freezer (15 cu ft) | 500 | 1,500 |
| Climatisation centrale (3 tonne, 14 SEER) | 3,500 | 6,000-8,000 |
| Fenêtre AC (12,000 BTU) | 1,200 | 3,600 |
| Pompe de puits (1 HP, 230V) | 1,500 | 4,500 |
| Pompe de puisard (1/2 HP) | 800 | 2,400 |
| Furnace blower (1/2 HP) | 800 | 2,400 |
| Electric water heater (4,500W) | 4,500 | 4,500 (resistive) |
| Micro-ondes | 1,200 | 1,200 |
| Lumières LED (10 bulbs) | 100 | 100 |
| TV + router + modem | 300 | 300 |
| Electric oven (single element) | 2,500 | 2,500 (resistive) |
| Clothes washer | 500 | 1,500 |
| Electric dryer | 5,500 | 5,500 (resistive) |
Étape 3: Apply the Load Calculation
Formule: Generator KW = (Total Running Watts + Largest Starting Surge) ÷ 1,000 × 1.25 (facteur de sécurité)
Example calculation for a 2,000 sq ft home (Étage 2):
- Total cumulé: Réfrigérateur 700 + Congélateur 500 + Pompe de puits 1,500 + Furnace blower 800 + CA 3,500 + Lumières 100 + Electronics 300 + Micro-ondes 1,200 = 8,600 watts
- Largest starting surge: AC compressor = 7,000 watts (during the 2 seconds the AC starts, everything else is running)
- Total surge requirement: 8,600 + 7,000 = 15,600 watts
- Avec 25% facteur de sécurité: 15,600 × 1.25 = 19,500 watts → 20 KW generator minimum
Recommended Diesel Generator Sizes by Home Type
| Home Type | Typical Size | Générateur recommandé | Estimated Fuel (24h @ 75% charger) |
|---|---|---|---|
| Small apartment / tiny home (Étage 1 only) | 5-8 KW | 8 KW SC Series | 15-20 L diesel |
| Medium home 1,500 pieds carrés (Étage 1 + partial comfort) | 10-15 KW | 15 KW YC Series | 30-40 L diesel |
| Large home 2,500 pieds carrés (Étage 2, one AC) | 20-25 KW | 20 KW SC or 25 KW YC | 50-65 L diesel |
| Large home 3,000+ pieds carrés (Étage 3, dual AC) | 30-50 KW | 30-50 KW SC/YC Series | 70-120 L diesel |
| Estate / farm with outbuildings | 50-100+ KW | 100 KW WC Series | 150-250 L diesel |
Important Considerations
Single-Phase vs Three-Phase
Most homes in North America use single-phase 120/240V split-phase power. Ensure the generator is configured for single-phase output. Triphasé Générateurs can be used for homes but require a phase converter or careful load balancing, and you’ll only access 58% of the three-phase rating on single phase.
Continuous vs Standby Rating
Diesel generators have two power ratings: Attendre (ESP) for emergency use, typiquement 100-200 heures par an, and Prime (PRP) for unlimited hours at variable load. For home backup, a standby-rated generator is sufficient and more economical. If you expect multi-day outages regularly, choose a prime-rated unit.
ATS (Commutateur de transfert automatique)
A properly sized ATS is essential. It must match the generator’s output amperage. Pour un 20 KW single-phase generator at 240V: 20,000 ÷ 240 = 83A. Choose a 100A-rated ATS. The ATS also determines whether you can power the entire house (whole-house switch) or only essential circuits (sub-panel with manual or automatic load shedding).
Stockage de carburant
Diesel fuel stores well (6-12 months with stabilizer, 18-24 months in underground tanks), contrairement à l'essence. Calculate storage needs: un 20 KW generator at 75% la charge consomme environ 4-5 L/heure. Pour 72 hours of continuous outage: 360L minimum. A 500L day tank provides a comfortable buffer.
FAQ
Q: Can I power my whole house with a 20 KW diesel generator?
UN: For most 2,000-2,500 sq ft homes with one central AC, yes—with load management. Without load management, un 20 KW generator may struggle if the AC, electric oven, and dryer all run simultaneously. Adding a load-shedding controller ($300-500) automatically prioritizes essential loads.
Q: What happens if my generator is undersized?
UN: Voltage and frequency sag under overload. Motor-driven appliances (CA, réfrigérateur) burn out from low voltage. The generator’s circuit breaker trips. Repeated overload shortens engine life. In worst case, the generator stalls while connected to the house.
Q: Is it better to oversize a home generator?
UN: Slightly oversizing (20-30%) is good practice. Severely oversizing causes “empilement humide”—unburned fuel accumulates in the exhaust system because the engine never reaches operating temperature at very light loads. This reduces efficiency and damages the engine. Aim for 50-80% loading during typical outage conditions.
Q: How far from the house should a diesel generator be placed?
UN: NFPA 37 requires a minimum of 5 feet from any openings (fenêtres, portes, vents) et 5 feet from combustible walls unless the wall has a 1-hour fire rating. For noise comfort, 20+ feet is recommended. Check local codes—many municipalities have stricter requirements.
Q: Do I need a concrete pad?
UN: Oui, a reinforced concrete pad is standard. Minimum 4 inches thick, extending 6 inches beyond the generator base on all sides. For larger units (au-dessus de 30 KW), 6-inch reinforced concrete is recommended. Pre-cast pads are available for smaller units.
Articles connexes
- Guide de consommation de carburant des générateurs diesel
- Diesel Generator for Construction Sites
- Diesel Generator Lifespan Guide
- Generator Noise Reduction Schemes
- Low Cost Diesel Generators Brand Evaluation
- Environmentally Friendly Generator Configurations
Recommended Home Backup Generators
- SC Series Diesel Generator Set — 20-80 KW, ideal for home backup
- Groupe électrogène diesel série YC — 20-250 KW, fuel-efficient